refrigerators-danfoss-without-correction

Danfoss controllers that regulate refrigerators in stores have six new, unpatched vulnerabilities. An update isn't enough: the equipment must be taken offline.

Following the wave of attacks in which the refrigerators at stores in France, other European countries, and Romania (six stores belonging to the same chain, according to DNSC), Dutch researchers at Midnight Blue discovered six new vulnerabilities in the Danfoss AK-SM800A controller. These vulnerabilities allow for complete takeover of the equipment without a password.

What's different from the original advice:

  • All software versions up to and including 5.3.2 are affected, and researchers say that even version 5.4.0 does not fix the vulnerabilities. The German agency BSI initially announced that version 5.4.0 was not affected, but later corrected its statement: it cannot rule out the possibility at this time.
  • Danfoss has not issued an advisory for these vulnerabilities, and a fix is not yet available.
  • Five of the vulnerabilities are in web pages that do not require authentication and run with maximum privileges; the sixth even bypasses the “Strict” security mode, which had been recommended until now.

There is currently no evidence that these six vulnerabilities were exploited in the attacks on refrigerators in stores. However, the exploit tools posted online are easy to find, and agencies in Belgium (CCB), Ireland (NCSC), and Germany (BSI) are calling for the same immediate action.

This applies to you if you own a store, a restaurant, a pharmacy, or a warehouse with a refrigeration system maintained remotely by a service company: that controller is often connected directly to the internet, sometimes via a 4G/5G modem separate from the company’s network.

What you need to do:

  • Ask the refrigeration service company if you have a Danfoss AK-SM800A controller (or one from the AK-SM 8xxA series) and if its management interface is accessible via the internet, including through a mobile modem.
  • Request that it be taken offline even if the software is up to date and “Strict” mode is enabled; allow remote access only via VPN. Allowing access only from the service provider’s IP address is a temporary solution.
  • Check the set temperatures, defrost schedule, alarms, and accounts; if anything appears to have been altered, change all passwords and check the equipment connected to the controller.

This article was generated with AI assistance.